Acrel Adw210-D10-1s Modular Multi Loop AC Multi Circuit Iot DIN Rail Electricity Power Meter Energy Meter
Product Description ADW210-D10-1S lcd display three phase multi channel smart IOT wireless modular submetering energy me;
Basic Info
Model NO. | ADW210-D10-1S |
Measured Signal | Continuous Wave |
Type | Energy Meter |
Certification | RoHS, ISO, CE |
Customized | Non-Customized |
Product Name | Three Phase Multi Channel Energy Meter |
Auxiliary Power | AC/DC 85V~265V |
Frequency | 45~65Hz |
Input Voltage | AC 3*220V/380V |
Input Curernt | AC 5A, 100A, 400A, 600A |
Accuracy | Class 0.5 |
Communication | RS485, Modbus-RTU |
Transport Package | Fob Shanghai |
Trademark | ACREL |
Origin | China |
Production Capacity | 1000PCS/Per Month |
Product Description
ADW210-D10-1S lcd display three phase multi channel smart IOT wireless modular submetering energy meterGeneral
ADW2XX series rail type multi-loop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits,Up to four three-phase loop current inputs can be connected simultaneously.It Can measure voltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters.Function1.Full electric parameter measurement of N(1,2,3,4) three-phase circuit,externalCurrent transformer;2.Monitoring three Phase Voltage/Current,Zero sequence Current,Frequency;3.Monitoring three Phase power ,total power (active,reactive,apparent);4.Monitoring three Phase power-factor,totalpower-factor;5.Monitoring Voltage/Current Phase Angle,Voltage/Current Degree of unbalance;6.Monitoring Voltage,Current total Harmonic and 2-31 Fractional harmonics;7.Record of voltage,current and power extremum of current month and last month;8.Maximum Current,Maximum power demand and real time Current,real time power demand;9.200 event records,Record the action of DIDO;10.Support over-voltage, over-current, phase failure,DI linkage and other alarm output;11.4 time zones 14Periods rate setting;12.Four quadrant electric energy,12-month multi rate electric energy;13.31 days four quadrant and multi rate electric energy freezing,Positive and negative energy metering;14.2 channel Switching inputs,2 channel Switching outputs,RS485,Active pulse output(Switchable corresponding circuit).The following auxiliary functions can be extended through its RJ45 interface:15.(MK) 12 channel Switching inputs+4 channel Switching outputs;16.(MTL) 12 channel external NTC temperature +4 channel residual current measurement (leakage current);17.(AWT100-2G) 2G Wireless Communication18.(AWT100-4G) 4G Wireless Communication19.(AWT100-NB) NB-IoT Wireless Communication20.(AWT100-LoRa) LoRa Wireless Communication21(AWT100-LW) LoRaWAN Wireless Communication
Technical Parameters(Meter)
Auxiliary power | AC/DC 85~265V;consumption≤10VA; | |
input | Frequency | 45~65Hz; |
Voltage | AC 3×220V/380V; | |
Overload: 1.2 times of rated value (continuous); 2 times of ratedvalue / 1s; | ||
Power consumption:≤ 0.5VA; | ||
Current | AC 5A,100A,400A,600A;(External opening transformer) | |
Overload: 1.2 times of rated value (continuous); 10 times of ratedvalue / 1s; | ||
Power consumption:≤ 0.5VA; | ||
measurement accuracy | Frequency 0.05Hz, voltage and current 0.5 level, active electricenergy level 1, reactive electric energy level 2; |
2-31 times harmonic accuracy: ± 1%; | |||
Features | Pulse output | Output mode: optocoupler pulse with open collector; | |
Communication | RS485,Modbus-RTU;Baud rate 1200~38400; | ||
Switchin g | input | Dry contact input,Built in power supply; | |
output | Output mode:Relay normally open contact output;contact rating:AC 250V/3A DC 30V/3A; |
Technical Parameters(Module)
Switching Module | Power | RJ45 interface,DC 12V,Power consumption≤1W; |
Communication | RJ45 interface,Modbus-RTU;(Communication with the main Part) | |
Switching input | Dry contact input,Built in power supply; | |
Switching output | Output mode:Relay normally open contact output;contact rating:AC 250V/3A DC 30V/3A; | |
Temperature and leakage module | Power | RJ45 interface,DC 12V,Power consumption≤1W |
Communication | RJ45 interface,Modbus-RTU;(Communication with the main Part) | |
temperaturemeasurement | -20~100ºC; | |
Leakage measurement | 10~3000mA; | |
measurement accuracy | temperature ±2ºC,Leakage1.0%; |
Other Parameters
Safety | Power frequencywithstand voltage | >AC 2kV/1min; |
Insulation resistance | >100MΩ; | |
Environment | working temperature:-20ºC~+60ºC; Storage temperature:-40ºC~+70ºC; relative humidity:≤95% No condensation; Altitude:≤2500m; | |
electromagnetic compatibility | Better than grade 3; |
Dimension(Unit:mm)
ADW2xx series main part dimension
Module dimension
Dimension(CT)
Installation
Wiring
Quotation
You may also like
Send inquiry
Send now