Power Factor Transducer

Power Factor Transducer

FUD-PF POWER FACTOR TRANSDUCER As the leading product in market, FUD-PF single phase/3P3W/3P4W power factor transducer a;
Basic Info
Model NO. FUD-PF
PF Range C1: 0(C)-1-0(L), C2: 0.5(C)-1-0.5(L), C3: 0-1
DC Output O1: 0-5V, O2: 1-5V, O3: 0-20mA, O4: 4-20mA, O5: 0-
Transport Package Standard Export Box
Specification EN 61010-1, CE, ISO9001: 2008, IEC
Trademark GUFVE
Origin Beijing, China
Production Capacity 10000PCS/ Month
Product Description

FUD-PF POWER FACTOR TRANSDUCER
As the leading product in market, FUD-PF single phase/3P3W/3P4W power factor transducer adopts the SCM as the core with the latest algorithm to achieve precise measurement of power-factor in AC circuit.

FEATURES
Single phase power factor transducer
3P3W power factor transducer
3P4W power factor transducer
Adopts the SCM as the core technology
With the latest algorithm

MODEL DESCRIPTION

FUD-Type-Input-Power Supply-PF range-Output
TypeCosφ: single phase power factor transducer
3Cosφ: 3P3W power factor transducer
4Cosφ: 3P4W power factor transducer
AC inputV0: 57V, V1: 100V, V2: 220V, V3: 270V,
V4: 400V, V5: User defined; A1: 1A, A2: 5A
Power supplyP1: AC110V±10%, P2: AC220V±15%
PF rangeC1: 0(C)-1-0(L), C2: 0.5(C)-1-0.5(L), C3: 0-1
DC outputO1: 0-5V, O2: 1-5V, O3: 0-20mA, O4: 4-20mA, O5: 0-5V, O6: 4-12-20mA, O7: RS485
Example 1: FUD-Cosφ-V2-A2-P2-C2-O6
FUD Single phase power factor transducerInput: AC220, 5A
Power: AC220V±15%
Range: 0.5(C)-1-0.5(L)
Output: DC4-12-20mA
Example 2: FUD-3Cosφ-V2-A2-P2-C2-O6
FUD Three phase power factor transducerInput: DC 0-300V
Power supply: AC220V±15%
Output: DC4-20mA
Please check the type, input range, output range and power supply when your order the product.

TECHNICAL INDEX

Technical Index
StandardGB/T 13850-1998, IEC688:1992
Accuracy0.5%
Consumption≤5VA
Insulation voltageAC 2kV/min.1mA (Between input- output / power)
Insulation resistance≥20MΩ (DC500V)
Response time≤300ms
Input rangeAC 0-6A, 0-380V(Option), 50/60Hz
Absorbed powerPer phase voltage: ≤0.5VA/220V
Per phase current: <0.1VA/5A
OverloadCurrent: 2 times continuous, 20 times /1s;
Voltage: 2 times continuous
Load resistanceCurrent output: RL≤650Ω
Voltage output: RL≥2kΩ
Working environmentTemperature: -10 to +50ºC
RH: 20-90%, without condensation
Storage conditionsTemperature: -40 to +70ºC
RH: 20-95%, without condensation
Installation35mm DIN sliding-way or M4 screws
Dimension110mm x 75mm x 120mm